Clean up time in clean room (Not uni-direction flow type)

31/01/2021, 04/10/2024
Hideki Miki, Ph.D. (Engineering), JICA Expert


Calculation
Note1: Error handling is minimal.
Note2: Tested with Chrome and Internet Explorer. (blocks must be removed.)

Fomula
t=log10(C0/C)/akn
C: Particle concentration (t hours later)[pcs/m3]
C0: Particle concentration (initial)[pcs/m3]
a: Correction value (from 0 to 1, around 0.6 (normal)[-]
k: Constant(=log10e≒0.4343)[-]
n: Air changing rate[times/hour]