Clean up time in clean room (Not uni-direction flow type)
31/01/2021, 04/10/2024
Hideki Miki, Ph.D. (Engineering), JICA Expert
Calculation
Note1: Error handling is minimal.
Note2: Tested with Chrome and Internet Explorer. (blocks must be removed.)
Fomula
t=log10(C0/C)/akn
| C | : |
Particle concentration (t hours later) | [pcs/m3] |
| C0 | : |
Particle concentration (initial) | [pcs/m3] |
| a | : |
Correction value (from 0 to 1, around 0.6 (normal) | [-] |
| k | : |
Constant(=log10e≒0.4343) | [-] |
| n | : |
Air changing rate | [times/hour] |
| t | : |
Time since operation started | [hour] |